Secure account setup

Connect a sensor that has arrived

Select an owned tank that will use an already provisioned sensor. You can scan its one-time Waterwise claim QR or enter the printed manual claim code on the next screen.

  1. 1. Confirm modelPlan resumed; secure identity follows.
  2. 2. Select assetChoose an owned tank below.
  3. 3. Configure pathUse released provisioning only.
  4. 4. Mount & calibrateRecord exact site requirements.
  5. 5. Verify readingWait for valid live telemetry.

Five-scenario prototype hold: WW-KIT-POLY, WW-KIT-METAL, WW-KIT-CONCRETE, WW-KIT-DAM-WALL and WW-KIT-DAM-BOWL are field-test candidates, not released sale stock. EM410 claims remain unavailable until inventory, decoder, field evidence and named QA release are approved.

Installation and activation gates

Claiming identifies hardware only. It does not mark a sensor online, its measurements verified, or an installation active.

  1. Match exact device identity, custom revisions, commercial SKUs and site.
  2. Record the AU915/OTAA profile and gateway channel plan.
  3. Pass controlled fixtures with the pinned EM410 decoder revision.
  4. Control scenario, range, datum, reporting and credentials.
  5. Pass mechanical QA for orientation, witnesses, tether and photos.
  6. Show error no greater than max(20 mm, 1% of tested span) against an independent reference.
  7. Show current distance or level, battery, tilt, signal, time and quality.
  8. Trace the raw payload through to the displayed result.
  9. Recover from an approved interruption within 15 minutes and distinguish replay.
  10. Record a named reviewer and date with no critical open item.

Next action: select an owned tank

Loading your tanks...